Huawei FusionModule500 User Manual page 252

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Maintenance
Area
Issue 02 (2020-12-25)
Maintenance
Item
Battery
appearance
Battery operating
temperature
Battery
management
parameter settings
Copyright © Huawei Technologies Co., Ltd.
Operation
-
-
-
Expected Result
Troubleshootin
g
1. The surface is
If the battery
clean and tidy
appearance is
without
abnormal,
stains.
contact Huawei
technical
2. The battery
support.
terminals are
intact.
3. Batteries are
free from
damage and
cracks.
4. Batteries are
free from acid
leakage.
5. Batteries are
not deformed
or bulged.
1. Battery
1. Identify the
operating
temperature:
0–45°C
(charging); –
20°C to +45°C
(discharging)
2. If the fault
2. Battery
charge and
discharge
conditions
meet the
requirements
specified in
the battery
specifications.
Check that the
Set parameters
settings of
correctly.
battery
management
parameters meet
the requirements
in the user
manual.
6 O&M
cause of an
abnormal
battery
operating
temperature.
persists,
contact
Huawei
technical
support.
242

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c00

Table of Contents