Space Requirements
Figure 4-18 Space requirements
4.2.4.5.2 Securing an Outdoor Unit
Prerequisites
●
●
Issue 02 (2020-12-25)
At a high place with strong winds, install the outdoor unit against a wall to
ensure the normal operating of fans. Install a baffle plate when necessary to
prevent the outdoor unit from toppling in strong winds.
Install an outdoor unit against a wall if possible. If the site conditions cannot
meet the requirements and the local outdoor temperature may be below –
10°C, install a baffle plate by referring to the space requirements. The baffle
plate height and width should be greater than or equal to the outdoor unit
height and width, respectively.
If the site installation environment is complicated and the preceding
conditions are not met, contact Huawei technical support.
The M10 expansion bolts used for securing an outdoor unit have been
prepared.
The concrete groundwork is prepared.
Copyright © Huawei Technologies Co., Ltd.
4 Installation Guide
80