Huawei FusionModule500 User Manual page 183

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Table 5-7 Setting device addresses
Address
1
2
Step 2 Add a T/H sensor.
1.
2.
3.
Step 3 Check the function of the T/H sensor.
Table 5-9 Function check
Check Method
Check the running
information about the T/H
sensor on the WebUI.
Issue 02 (2020-12-25)
Toggle
Switch 1
ON
OFF
Log in to the ECC800-Pro WebUI as an administrator.
Add a T/H sensor.
Table 5-8 Adding a T/H sensor
Path
Parameter
Choose
Device
System
Attribute
Settings >
Device Type
Device
Management
and click Add
Connect To
Device.
Communica
tions Port
Device
Address
Click Test Connect to check whether the T/H sensor connects to the ECC800-
Pro properly.
If the connection is normal, click Confirm. The connected devices are
displayed in the Number of connected devices list.
If the connection is abnormal, check whether the device is properly
connected to the ECC800-Pro, whether the device and the ECC800-Pro are
running properly, and whether the parameter settings are consistent with
the device parameters.
Copyright © Huawei Technologies Co., Ltd.
Toggle
Toggle
Switch 2
Switch 3
OFF
OFF
ON
OFF
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
In this example, Device Address is set to 1.
During actual configuration, set the device
address for the T/H sensor based on the
actual situation.
Normal Connection Status
Choose Monitoring > Aisle > T/H Sensor Group
> T/H Sensor n > Running Info, and view the
current cabinet temperature and humidity.
5 Power-On Commissioning
Toggle
Toggle
Switch 4
Switch 5
OFF
OFF
OFF
OFF
Toggle
Switch 6
OFF
OFF
173

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c00

Table of Contents