HUAWEI Eudemon8000E Firewall
Hardware Description
If the power supply distance is longer than 35 m, you need to place the DC power distribution
cabinet near the E8000E-X3. For cables to be selected, see
Than or Equal to 15
You need to prepare suitable cables according to the surveyed power supply distance between
the E8000E-X3 and the DC power distribution cabinet.
Power Supply Distance Shorter Than or Equal to 15 m
If the power supply distance is shorter than or equal to 15 m, use the 16 mm
connect the Eudemon8000E and the DC power distribution
terminals and cable types.
Table 6-7 Cable used when the power supply distance is shorter than or equal to 15 m
Item
Cable type
Terminal
Power Supply Distance Longer Than 15 m and Shorter Than or Equal to 35 m
If the power supply distance is longer than 15 m and shorter than or equal to 35 m, use the 25
mm
6-8
Table 6-8 Cables used when the power supply distance is longer than 15 m and shorter than or
equal to 35m
Item
Cable type
Issue 01 (2012-11-07)
CAUTION
m.
NEG power
cable (-48 V)
RTN power
cable
E8000E-X3
DC Power
distribution
cabinet
2
power cable to connect in the E8000E-X3 and the DC power distribution cabinet.
lists the cable terminals and cable types.
NEG power
cable (-48 V)
RTN power
cable
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Description
Wire,450/750V,60227 IEC 02(RV)16mm
Wire,450/750V,60227 IEC 02(RV)16mm
Naked Crimping Terminal,JG2,16mm
Plated,for OEM
Naked Crimping Terminal,OT,16mm
Plating,Naked Ring Terminal
Description
Wire,450/750V,227 IEC 02(RV)25mm
Wire,450/750V,227 IEC 02(RV)25mm
Power Supply Distance Shorter
2
power cable to
cabinet.Table 6-7
lists the cable
2
,blue,85A
2
,black,85A
2
,M6,95A,Tin
2
,M8,Tin
2
,blue,110A
2
,black,110A
6 Cables
Table