7.14.2
Digital inputs (DI)
The Softstarter has 5 digital inputs for basic control of the
unit.
The 5 digital inputs are terminal 13, 14, 15, 16 and 17.
The inputs are named
• Start
• Stop
• In0
• In1
• In2
Start and Stop inputs are fixed to start and stop function
and cannot be changed.
In0, In1 and In2 are programmable inputs. Functions can
be related to the physical signal through a drop down
menu on the HMI.
Use the inputs with 24 V and current sinking type, 10 mA.
The digital input is isolated and can withstand up to 100 V
in potential difference between the Softstarter functional
ground and the ground of the interconnected system. You
can use the input with internal 24 V or external 24 V supply.
The digital input values for respective input voltage:
"0" = 0 – 5 V
"1" = 15 – 33 V
Maximum voltage input is 33 V and minimum is -0.5
V. Outside these voltage ranges the digital value is
undefined and can be either "0" or "1".
Internal digital Inputs (Internal I/O) have these
parameters:
Parameter
Description
10.01 In0 function
Function of programmable digital
input.
10.02 In1 function
10.03 In2 function
External digital Inputs (extension I/O) have these
parameters:
Parameter
Description
11.01 1DI0 function
Function of programmable digital
input.
11.02 1DI1 function
Same as 1DI0
11.03 1DI2 function
Same as 1DI0
11.04 1DI3 function
Same as 1DI0
11.05 1DI4 function
Same as 1DI0
11.06 2DI5 function
Same as 1DI0
11.07 2DI6 function
Same as 1DI0
11.08 2DI7 function
Same as 1DI0
Setting range
None, Reset, Enable, Slow speed forward, Slow
speed reverse, Motor heating, Stand-still brake,
Start reverse, User defined protection, Emergency
mode (active high), Emergency mode (active low),
Fieldbus disable control, Start 1, Start 2, Start 3,
Switch to remote control, Cancel brake, Pump
cleaning automatic, Pump cleaning forward, Pump
cleaning backward, Hold in Remote (Active High),
Hold in Remote (Active Low), Lock Parameters
(Active High), Lock Parameters (Active Low).
Same as In0
Same as In0
Setting range
None, Reset, Enable, Slow speed forward, Slow
speed reverse, Motor heating, Stand-still brake, Start
reverse, User defined protection, Emergency mode
(active high), Emergency mode (active low), Fieldbus
disable control, Start 1, Start 2, Start 3, Switch
to remote control, Cancel brake, Pump cleaning
automatic, Pump cleaning forward, Pump cleaning
backward, Hold in Remote (Active High), Hold in
Remote (Active Low), Lock Parameters (Active
High), Lock Parameters (Active Low).
Same as 1DI0
Same as 1DI0
Same as 1DI0
Same as 1DI0
Same as 1DI0
Same as 1DI0
Same as 1DI0
1SFC132081M0201
| Installation and commissioning manual | Functions
7
Default value
Reset
None
None
Default value
Reset
None
None
None
None
None
None
None
93