7.25 Complete parameter list
Parameter
Description
number
01
Motor rated current Ie
01.01
Motor rated current Ie
02
Start and stop
02.01
Start mode
02.02
Stop mode
02.03
Start ramp initial level
02.04
Start ramp time
02.05
Stop ramp end level
02.06
Stop ramp time
02.07
Pre-start function
02.08
Pre-start time
03
Limit
03.01
Current limit type
03.02
Current limit level
03.03
2nd curr lim level
03.04
2nd curr lim time
03.05
Torque limit level
04
Kick start
04.01
Kick start
04.02
Kick start level
04.03
Kick start time
05
Slow speed
05.01
Slow speed forward
05.02
Slow speed fwd strength
05.03
Slow speed reverse
05.04
Slow speed rev strength
06
Motor heating
06.01
Motor heating capacity
06.02
Motor heating temperature
06.03
Motor heating type
07
Motor braking
07.01
Stand still brake strength
07.02
Motor brake time
07.03
Dynamic brake strength
07.04
DC brake strength
07.05
DC brake switch speed
threshold
07.06
DC brake switch delay time
08
Sequence start
08.01
Sequence mode
08.02
Ie seq 1
08.03
Start mode seq 1
08.04
Start ramp time seq 1
08.05
Start ramp init lvl seq 1
08.06
Curr lim level seq 1
08.07
Kick start seq 1
08.08
Kick start level seq 1
08.09
Kick start time seq 1
08.10
Torque lim lvl seq 1
08.11
Torque tune seq 1
08.12
Torque ctrl gain seq 1
08.30
Ie seq 2
08.31
Start mode seq 2
Setting range
9.0 ... 1250.0 A
Voltage ramp, Torque ramp, Full voltage start
No ramp, Voltage ramp, Torque ramp
10 ... 99%
1 ... 120 s
10 ... 99%
1 ... 120 s
Pre start off, Motor heating, Stand still brake
Slow speed forward, Slow speed reverse
0.0 ... 7200.0 s
Off, Normal, Dual, Ramp
1.5 ... 7.5 x I e
0.5 ... 7.5 x I e
2 ... 120 s
20 ... 200%
On / Off
50 ... 100%
0.2 ... 2.0 s
Fast jog, Jog, Creep
10 ... 100%
Fast jog, Jog, Creep
10 ... 100%
10 ... 100000 W
10 ... 100000 W
Off, Manual
10 ... 100
1.0 ... 100.0 s
10 ... 100 %
10 ... 100 %
10 ... 100 %
0.1 ... 100.0 s
On / Off
9.0 ... 1250.0 A
Voltage ramp, Torque ramp, Full voltage start
1 ... 120 s
10 ... 99%
0.5 ... 7.5 x I e
On / Off
50 ... 100%
0.20 ... 2.0 s
20 ... 200%
0 ... 1000%
0.01 ... 10.0
9.0 ... 1250.0 A
Voltage ramp, Torque ramp, Full voltage start
1SFC132081M0201
Number of
Fieldbus
decimals
ID
1
1
0
2
0
3
0
4
0
5
0
6
0
7
0
93
1
128
0
18
1
19
1
20
0
21
0
170
0
22
0
23
2
24
0
184
0
187
0
188
0
189
0
304
0
0
305
1
0
0
0
1
0
8
1
190
0
191
0
192
0
193
1
194
0
195
0
196
2
197
0
198
0
199
2
200
1
201
0
202
| Installation and commissioning manual | Functions
Default value
Actual
setting
30 A
Voltage ramp
No ramp
30%
10 s
30%
10 s
Pre start off
10.0 s
Off
4.0 x I e
7.0 x I e
8 s
150%
Off
70%
0.20 s
7
Jog
50%
Jog
50%
10 W
10 W
Off
50%
1.0 s
40 %
40 %
28 %
3.0 s
Off
30 A
Voltage ramp
10 s
30%
7.0 x I e
Off
70%
0.20 s
150%
100%
0.02
30 A
Voltage ramp
133