ABB PSTX Series Installation And Commissioning Manual page 22

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

3.2
Technical data
3.2.1
General
Table 3
General
General data
24 V output
Rated insulation voltage,
Ui
Rated operation voltage,
Ue
Rated supply voltage,Us
Voltage tolerance
3
Rated frequency
Frequency tolerances
Rated impulse withstand
voltage
Relay outputs
Number of controlled
phases
Inputs
Outputs
Output relay
performance
Analog output
PTC input
Cooling system
Recommended fuse
Control supply circuit
Communication
Communication
protocols
3.2.2
Technical data for external keypad
Table 4
Technical data for external keypad
Display
Status indicating LEDs
Ambient temperature
Degree of protection
UL approval
Marine approvals
22
Description | Installation and commissioning manual |
Description
24 V ± 5% Max 250 mA
600 V / 690 V
208-600 / 690 V, 50 / 60 Hz
100-250 V, 50 / 60 Hz
+10% to -15%
50 / 60 Hz
± 10%
6 kV Operation circuit
4 kV Control and supply circuit
3 programmable
3
Start, stop, 3 programmable inputs
(Digital I/O: In0, In1, In2), temperature
sensor input.
Relay outputs: K4 K5 K6.
250 V AC, Ith = 5A, Ie = 1.5A (AC-15)
4-20 mA, 0-20 mA, 0-10 V, 0-10 mA
2825 ohm ± 20% switch off resistance
1200 ohm ± 20% switch on resistance
Fan
6 A Delayed
MCB use C characteristics
3 Fieldbus ports, Extension I/O
DeviceNet / Profibus DP / Modbus /
EtherNET/IP / Modbus TCP/ Profinet
Display type
Ready:
Green
Run:
Green
Protection:
Yellow
Fault:
Red
Storage: -25 °C to +70 °C (-13 °F
to 158 °F)
Operation: -25 °C to +60 °C
(-13 °F to 140 °F)
IP66
Type 1
Type 4X
Type 12
Speak to your ABB sales office
3.2.3
Semi-conductor fuses
WARNING!
Semiconductor fuses must be used to keep the
warranty on the thyristors.
INFORMATION
To achieve a type 2 coordination, semiconductor
fuses must be used.
Table 5
Fuses ratings and power losses
Current
range
Type
A
PSTX30
9.0...30.0
PSTX37
11.1...37.0
PSTX45
13.5...45.0
PSTX60
18.0...60.0
PSTX72
21.6...72.0
PSTX85
22.5...85.0
PSTX105
31.8...106.0
PSTX142
42.9...143.0
PSTX170
51.3...171.0
PSTX210
63.0...210.0
PSTX250
75.0...250.0
PSTX300
90.0...300.0
PSTX370
111.0...370.0
PSTX470
141.0...470.0
PSTX570
171.0...570.0
PSTX720
216.0...720.0
PSTX840
252.0...840.0
PSTX1050
3)
315.0...1050.0
3) 4)
PSTX1250
375.0...1250.0
1)
For the supply circuit 6 A delayed, for MCB use C characteristics.
2)
For inside delta connection the fuses shall be placed inside the delta. Contact ABB for
more information.
3)
170M6019 with fuse rating 1600 A should be used for 690 V version.
4)
For 690 V version, Bussmann fuses are only available for motors with rated current up
to 1150 A.
You can find more detailed information at:
http://applications.it.abb.com/SOC/
3.2.4
Weights
Table 6
Weights
Type
PSTX30...105
PSTX142...170
PSTX210...370
PSTX470
PSTX570
PSTX720 ...840
PSTX1050
PSTX1250
1SFC132081M0201
Max
Max fuse raiting - main
1) 2)
circuit
power
Bussmann fuses, DIN43 620
loss at
(Knife)
rated I
e
W
A
Type
Size
0.8
100
170M1567 000
1.2
125
170M1568 000
1.8
160
170M1569 000
3.2
160
170M1569 000
4.7
250
170M1571 000
6.5
315
170M1572 000
10
400
170M3819 1*
18
500
170M5810 2
26
630
170M5812 2
48
630
170M5812 2
68
700
170M5813 2
97
800
170M6812 3
148
900
170M6813 3
99
900
170M6813 3
146
1000
170M6814 3
78
1250
170M8554 3
106
1500
170M6018 3
165
1800
170M6020 3
234
2000
170M6021 3
Weight in kg
Weight in lbs
6,1
13,5
9,6
21,2
12,7
27,9
25.5
55.1
27.5
59.5
46.2
101.4
64.5
141.1
65
143.3
Power
require-
ments
supply
circuit
Holding
(VA) /
Pull-in
(VA)
49/51
49/51
49/51
49/51
49/51
49/51
49/51
49/53
49/53
56/276
56/276
56/276
56/276
67/434
67/434
61/929
61/929
68/929
68/929

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents