ABB PSTX Series Installation And Commissioning Manual page 88

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

Motor braking has these parameters:
Parameter
07.01 Stand still brake strength
07.02 Motor brake time
07.03 Dynamic brake strength
07.04 DC brake strength
07.05 DC brake switch speed
threshold
07.06 DC brake switch delay time
02.02 Stop mode
28.51 Firing angle sweep
28.52 Auxiliary condition
28.53 Flux threshold gain 1
7
28.54 Flux threshold gain 2
88
Functions | Installation and commissioning manual |
Description
Sets the braking strength, choose suitable
value for application.
Sets the motor brake time.
Sets the Dynamic braking strength.
Sets the DC braking strength.
The approximate speed when the switch from
dynamic brake to DC brake occurs.
Sets the time that the speed has be below
the threshold before the switch to DC brake
occurs. Configure this parameter only if the
switch occurs too soon or too late.
Sets the desired stop mode: No ramp =
Immediately cuts power to the motor, Voltage
stop ramp = Decreases voltage linearly,
Torque stop ramp = Decreases torque in a
pre-defined pattern, Dynamic brake = Applies
brake to the motor
Enables dynamic optimization of dynamic
brake
Enables additional thyristor trig occasions of
dynamic brake
Flux threshold for thyristor trig of dynamic
brake
Flux threshold for speed estimation of
dynamic brake
1SFC132081M0201
Setting range
10 – 100%
1.0 – 100.0 s
10-100%
10-100%
10-100%
0.1 – 100.0 s
No ramp/Voltage stop ramp/
Torque stop ramp/Dynamic
brake
Off, On
Off, On
0.0 – 1.0
0.0 – 1.0
Default value
50%
1.0 s
40%
40%
28%
3.0 s
No ramp
On
Off
0.022