Programmable inputs - terminals 15, 16
5.1.2.4
and 17
WARNING
Use only 24 V DC to connect terminal 13, 14,
15, 16 and 17. Other voltages can damage the
Softstarter and the warranty will no longer be
valid.
The Softstarter has 3 programmable inputs.
In0, default reset event.
In1, default none
In2, default none
For programming the Softstarter inputs, see chapter 7.14
Inputs/outputs.
Connect the cables, see Figure 5.11, and Figure 5.12
to use the internal control supply voltage, or Figure 5.11
and Figure 5.13to use an external source.
INFORMATION
Connections for sequence start,
5.1.2.5 Programmable inputs (Sequence
start)
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
see chapter
Start Stop
In0 In1 In2
GND
+24V
K6
K6
Start Stop
In0 In1 In2
GND
+24V
1SFC132081M0201
Figure 5.11
Terminals 16 and 17
L
N
100-250V
50/60 Hz
K4
K5
Figure 5.12
Programmable inputs, terminals 15, 16 and 17
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
L
N
100-250V
50/60 Hz
K4
K5
Figure 5.13
External control voltage
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
| Installation and commissioning manual | Connection
K6
Start Stop In0 In1 In2 DGND
GND
+24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
+
DC
-
K6
Start Stop
In0
In1 In2 DGND
GND
+24V
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
43