Parameter
Description
number
21.14
Current imbalance trip time
22
Warnings list 3
22.01
Over voltage level
22.02
Over voltage trip time
22.03
Over voltage out
22.04
Over voltage
22.05
Under voltage level
22.06
Under voltage trip time
22.07
Under voltage out
22.08
Under voltage
22.09
Voltage imb level
22.10
Voltage imb out
22.11
Voltage imbalance
22.12
Voltage imbalance trip time
23
Warnings list 4
23.01
EOL time-to-trip time
23.02
EOL time-to-trip out
23.03
EOL time-to-trip
23.04
THD(U) level
23.05
THD(U) out
23.06
THD(U)
23.07
Short circuit out
23.08
Short circuit
23.09
THD(U) trip time
24
Warnings list 5
7
24.01
Number of starts limit
24.02
Number of starts out
24.03
Number of starts
24.04
Faulty fan out
24.05
Faulty fan
24.06
Modbus_RTU w/o auxport out
24.7
Phase loss trip time
24.8
Phase loss out
24.9
Phase loss
24.10
Motor run time limit
24.11
Motor run time out
24.12
Motor run time
25
Internal faults
25.01
Shunt fault out
25.02
Shunt fault op
25.03
Short circuit out
25.04
Short circuit fault op
25.05
Open circuit thyr out
25.06
Open circuit thyr op
25.07
Thyristor OL out
25.08
Thyristor OL op
25.09
Heatsink over temp out
25.10
Heatsink over temp op
25.11
Unspecified fault out
25.12
Unspecified fault op
26
External faults
26.01
Phase loss out
26.02
Phase loss op
26.03
Bad network out
26.04
Bad network op
26.05
Low supply voltage out
26.06
Low supply voltage op
26.07
High current out
26.08
High current op
140
Functions | Installation and commissioning manual |
Setting range
0.1 ... 100.0
208 ... 850 V
0.1 ... 100.0 s
Eventgroup 0 ... 6
On / Off
208 ... 850 V
0.1 ... 100.0 s
Eventgroup 0 ... 6
On / Off
1 ... 100
Eventgroup 0 ... 6
On / Off
0.1 ... 100.0 s
1 ... 1000 s
Eventgroup 0 ... 6
On / Off
1 ... 100%
Eventgroup 0 ... 6
On / Off
Eventgroup 0 ... 6
On / Off
0.1 ... 100.0 s
1 ... 65535
Eventgroup 0 ... 6
On / Off
Eventgroup 0 ... 6
On / Off
Eventgroup 0 ... 6
0.5 ... 100.0
Eventgroup 0 ... 6
On / Off
0 ... 100000
Eventgroup 0 ... 6
On / Off
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
Eventgroup 0 ... 6
Stop-Manual, Stop-Automatic
1SFC132081M0201
Number of
Fieldbus
Default value
decimals
ID
1
5.0 s
0
104
650 V
1
105
1.0 s
0
107
0000100
0
106
Off
0
108
208 V
1
109
0.5 s
0
111
0000100
0
110
Off
0
119
5
0
120
0000100
0
118
Off
1
5.0 s
0
114
5 s
0
112
0000100
0
113
Off
0
116
10%
0
117
0000100
0
115
Off
0
129
0000100
0
121
Off
1
10.0 s
0
-
65535
0
-
0000100
0
-
Off
0
80
0000100
0
79
On
0
176
0000100
1
3.0
0
0000100
0
Off
0
10000
0
0000100
0
Off
0
42
0000001
0
272
Stop-Manual
0
50
0000001
0
273
Stop-Automatic
0
44
0000001
0
274
Stop-Manual
0
47
0000001
0
275
Stop-Manual
0
48
0000001
0
276
Stop-Manual
0
43
0000001
0
277
Stop-Manual
0
96
0000001
0
278
Stop-Manual
0
36
0000001
0
279
Stop-Manual
0
46
0000001
0
280
Stop-Manual
0
49
0000001
0
281
Stop-Manual
Actual