Programmable inputs (Sequence start)
5.1.2.5
The Softstarter can start up to 3 different motors used
in different applications with different parameter sets.
The parameter set is chosen through input signals to the
Softstarter.
See Figure 5.14, Sequential start of motors using a
Softstarter.
If the Softstarter trips for any reason, and the trip must
stop the motor, all motors are stopped.
When you use sequence start, see Figure 5.15 or Figure
5.16 for the connection.
The start command (terminal 13, 14, 16 and 17) must be
maintained during operation, otherwise a direct stop is
done.
Soft stop can only be done for the motor currently fed by
the Softstarter, by giving a stop command (terminal 14).
5
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
44
Connection | Installation and commissioning manual |
Start Stop
In0 In1 In2
GND
K5
K6
K5
K6
Start Stop
In0 In1 In2
GND
KM 1
Q 1
K 25
Figure 5.14
Sequential start of motors using a Softstarter
L
N
100-250V
50/60 Hz
Figure 5.15
External control voltage
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
+24V
4,3 lb.in
L
N
100-250V
50/60 Hz
Figure 5.16
Internal control voltage
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
+24V
4,3 lb.in
1SFC132081M0201
KM 1
Main contactor
K 25, 27, 29
Starting contactor
K 26, 28, 30
Run contactor
FR 1, 2, 3
Overload relay
Q 1
Softstarter
K 26
K 28
K 30
K 27
K 29
FR 1
FR 2
FR 3
M
M
M
+
DC
-
Start Stop
In0
In1 In2 DGND
GND
+24V
K4
K5
K6
PSTX
AWG 12 ... 24
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
K4
K5
K6
Start Stop
In0
In1 In2 DGND
GND
+24V
PSTX
AWG 12 ... 24
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
0,2 .. 2,5 mm
2x0,2 .. 1,5 mm
2
2
2
2
2
2
2
2