11.2 Application diagrams
11.2.1
Inside Delta
O/I
2-wire control
E
O
K7
E
I
K7
K7
Inside Delta can be used with a lower rated Softstarter than for Inline. Parameter 01.01 Motor rated current Ie = 58%
of the Motor rated current listed in the Motor number plate. Coil consumption for Inside Delta contactor, Pull-in max
15A, Holding max 1.5 A. If the pull-in or holding values are higher, the Inside Delta contactor must be controlled via an
auxillary contactor.
11.2.2
Start at optional direction
O/I
E
O
K12
K12
E
I
E
II
K21
K22
K22
K21
K7
H1
K21
H2
K22
Forward
Reverse
Stop
Start at optional direction must be used to achieve the ability to run the motor at full speed both forward and reverse.
Before changing direction, motor must be stopped.
1
4
So Starter
PSTX
21
+ 24V
20
19 GND
18 DGND
17 In2
K4
16 In1
15 In0
14 Stop
13 Start
22
2
5
6
K3
3-wire control
20 +24V
E
O
E
14 Stop
I
13 Start
1
So starter
PSTX
21
+ 24V
20
19 GND
S21
S22
K7
18 DGND
17 In2
16 In1
K7
15 In0
14 Stop
13 Start
22
2
K12
1SFC132081M0201
| Installation and commissioning manual | Wiring and application diagrams
Anybus
7
10
Com 1
Com 2
23 +(B)
24 -(A)
25 T1
HMI
26 T2
K6
K5
27 T3
28 +24V
29 +
30 GND
8
9
11
12
4
7
10
Com 1
Com 2
23 +(B)
HMI
24 -(A)
K6
K4
K5
25 T1
26 T2
27 T3
28 +24V
29 +
30 GND
5
6
8
9
11
12
1L1
3L2
5L3
Alt. with fuses
F1.1
.2
.3
1L1
3L2
5L3
PSTX
K3
2T1
4T2
6T3
W1
W2
V1
V2
M
U1
U2
1L1
3L2
5L3
Alt. with fuses
F1.1
.2
.3
K22
K21
1L1
3L2
5L3
PSTX
2T1
4T2
6T3
2T1 4T2
6T3
M
11
171

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents