ABB PSTX Series Installation And Commissioning Manual page 138

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

Parameter
Description
number
14
Protections list 2
14.01
Curr underload level
14.02
Curr underload trip time
14.03
Curr underload delay time
14.04
Curr underload out
14.05
Curr underload op
14.06
Pwr factor underload level
14.07
Pwr factor underload trip
time
14.08
Pwr factor underload delay
time
14.09
Pwr factor underload out
14.10
Pwr factor underload op
14.11
Curr imb level
14.12
Curr imb trip time
14.13
Curr imb delay time
14.14
Curr imb out
14.15
Curr imb operation
15
Protections list 3
15.01
Over voltage level
15.02
Over voltage trip time
15.03
Over voltage out
15.04
Over voltage op
7
15.05
Under voltage level
15.06
Under voltage trip time
15.07
Under voltage op
15.08
Under voltage out
15.09
Voltage imb level
15.10
Voltage imb out
15.11
Voltage imb op
15.12
Voltage imb trip time
16
Protections list 4
16.01
Phase rev out
16.02
Phase rev operation
16.03
Freq range lower trip lvl
16.04
Freq range upper trip lvl
16.05
Freq range trip time
16.06
Freq range out
16.07
Freq range operation
16.08
Bypass open out
16.09
Bypass open operation
16.10
Voltage outputs out
16.11
Voltage outputs op
17
Protections list 5
17.01
PTC out
17.02
PTC op
17.03
PT100 2wire res
17.04
PT100 trip temp
17.05
PT100 reset temp
17.06
PT100 out
17.07
PT100 op
138
Functions | Installation and commissioning manual |
Setting range
0.3 ... 0.9 x I e
0 ... 10 s
0 ... 30 s
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
0.00 ... 1.00
0 ... 10 s
0 ... 30 s
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
10 ... 80%
1 ... 30 s
1 ... 30 s
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
170 ... 850 V
0.1 ... 100.0 s
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
165 ... 850 V
0.1 ... 100.0 s
Off, Stop-Manual, Stop-Automatic, Indication
Eventgroup 0 ... 6
1 ... 100%
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
1 ... 100 s
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
40 ... 72 Hz
40 ... 72 Hz
0.0 ... 60.0 s
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
0 ... 100.0 Ω
-50 ... 250 °C
-50 ... 250 °C
Eventgroup 0 ... 6
Off, Stop-Manual, Stop-Automatic, Indication
1SFC132081M0201
Number of
Fieldbus
Default value
decimals
ID
1
232
0.5 x I e
0
233
10 s
0
234
5 s
0
87
0000010
0
235
Off
2
236
0.50
0
237
10 s
0
238
5 s
0
86
0000010
0
239
Off
0
61
80%
0
63
10 s
0
62
5 s
0
64
0000010
0
60
Off
0
67
850 V
1
65
1.0 s
0
68
0000010
0
66
Off
0
71
165 V
1
69
1.0 s
0
70
Off
0
72
0000010
0
77
10%
0
78
0000010
0
76
Off
0
10 s
0
89
0000010
0
240
Off
0
241
45 Hz
0
242
66 Hz
1
243
5.0 s
0
91
0000010
0
244
Off
0
95
0000010
0
245
Indication
0
-
0000010
0
-
Indication
0
88
0000010
0
246
Off
1
247
5.0 Ω
0
248
60 °C
0
240
40 °C
0
98
0000010
0
250
Off
Actual
setting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents