ABB PSTX Series Installation And Commissioning Manual page 112

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

7.18 Warnings
The Softstarter has a number of warning functions to
signal malfunctioning or other potential risks, before
asserting the protection or fault. The difference between
a warning and a protection is that a warning cannot stop
the Softstarter and a reset of a warning is not necessary.
The warning level and all other additional information to
enable the warning can be set by the user.
A warning is stored in the event list. Warnings can be
Enable or Disable. There is sometimes a percentage
setting were the user can set at which percentage level
the warning occurs.
Set warnings to an Event group by the Out parameter.
The Event group can be set for relay output to control
other devices in an application.
As default, all parameters are set to the same
Eventgroup.
Warnings show on the HMI, but do not change the
behavior of the Softstarter.
7.18.1
Electronic overload warning
7
The motor temperature is higher than the set warning
level, % of max temperature.
Electronic overload warning has these parameters:
Parameter
20.01 EOL level
20.02 EOL out
23.03 EOL warning
7.18.2
Locked rotor warning
A warning signal will be given if the current exceeds the
settable warning level.
The motor is running stiff.
Locked rotor warning is configured with the
following parameters:
Parameter
20.04 Locked rotor level
20.05 Locked rotor init time
20.06 Locked rotor out
20.07 Locked rotor
20.10 Locked rotor trip time
112
Functions | Installation and commissioning manual |
Description
Sets the EOL warning level.
Identifies the Event groups this
warning is part of.
Enables EOL warning.
Description
Sets the Locked rotor warning level.
Sets the time delay after top of
ramp when the warning is enabled.
Identifies the Event groups this
warning is part of.
Enables locked rotor warning.
Sets the time that the rotor is
locked before trip.
1SFC132081M0201
Setting range
Default value
40.0 ... 99.0%
90.0%
Eventgroup 0 ... 6
0000100
Off, On
Off
Setting range
Default value
0.2 ... 10.0 x I e
1.2 x I e
1.0 ... 30.0 s
5 s
Eventgroup 0 ... 6
0000100
Off, On
Off
0.1...100.0 s
0.1 s