7.17.13 Voltage outputs protection
This protection senses if the 24 V voltage outputs is
overloaded or shorted.
Voltage outputs protection has these parameters:
Parameter
16.10 Voltage outputs out
16.11 Voltage outputs op
7.17.14 Temperature sensors
External thermal sensor - PTC
7.17.14.1
protection
The external thermal sensor detected a temperature
higher than the trip level. The Softstarter has a
temperature input where a PTC element can be
connected.
This can be set to trip if it goes above a certain
temperature.
External thermal sensor - PTC protection has these
parameters:
7
Parameter
10.11 Ext therm sensor - ID
17.01 PTC out
17.02 PTC op
External thermal sensor - PT100
7.17.14.2
protection
The external thermal sensor detected a temperature
higher than the trip level.
The Softstarter has a temperature input where a PTC100
element can be connected. This can be set to trip if it
goes above a certain temperature.
External thermal sensor - PT100 protection has
these parameters:
Parameter
10.11 Ext therm sensor - ID
17.03 PT100 2wire res
17.04 PT100 trip temp
17.05 PT100 PT100 reset temp
17.06 PT100 out
17.07 PT100 op
108
Functions | Installation and commissioning manual |
Description
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
Description
Sets the External thermal sensor
modes.
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
Description
Sets the External thermal sensor
modes.
Sets the 2-wire resistance for
PT100.
Sets the PT100 trip temperature
level.
Sets the PT100 reset temperature.
Identifies the Event groups this
protection is part of.
Sets the operation of this
protection.
1SFC132081M0201
Setting range
Default value
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Indication
Stop auto, Indication.
Setting range
Default value
No sensor, PTC,
No sensor
PT100-3Wire,
PT100-2Wire,
Bi-metal switch.
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Off
Stop auto, Indication.
Setting range
Default value
No sensor, PTC,
No sensor
PT100-3Wire,
PT100-2Wire,
Bi-metal switch.
0 ... 100 Ohm
5 Ohm
-50° ... 250°
60°
-50° ... 250°
40°
Eventgroup 0 ... 6
0000010
Off, Stop manual,
Off
Stop auto, Indication.