3
SPECIFICATIONS
(1) Transmission distance
Transmission Speed
Transmission Distance
9.6 kbps
19.2 kbps
1200 m (3937 ft.)/segment
93.75 kbps
187.5 kbps
1000 m (3281 ft.)/segment
500 kbps
400 m (1312 ft.)/segment
1.5 Mbps
200 m (656 ft.)/segment
3 Mbps
6 Mbps
100 m (328 ft.)/segment
12 Mbps
* 1 The max. transmission distance in the table above is based on the case where 3 repeaters are
used.
The calculation formula for the transmission distance extended using a repeater(s) is:
Max. transmission distance [m/network] =
(Number of repeaters + 1) x Transmission distance [m/segment]
3.1 Performance Specifications
Table3.2 Transmission Distance
Max. Transmission Distance when
4800 m (15748 ft.)/network
4000 m (13123 ft.)/network
1600 m (5249 ft.)/network
800 m (2625 ft.)/network
400 m (1312 ft.)/network
*1
Repeater is Used
3
- 2
1
2
3
4
5
6
7
8