TROUBLESHOOTING
(2) When the QJ71PB92D-compatible function is enabled
Parameters cannot be written.
Is any other than
GX Configurator-DP Version 7.00A
being used?
Yes
Is the DP-Master set to
"QJ71PB92D" in the "PROFIBUS Network" window
in GX Configurator-DP?
Yes
Has settings
configured in the "Transfer Setup" window
and the "Master Settings" window
in GX Configurator-DP?
Yes
Is 9244
set for Switch 2 of
H
the intelligent function module switches
in GX Works2?
Yes
Completed
Figure 9.4 When the QJ71PB92D-Compatible Function id Enabled
9.2 When Parameters cannot be Written from GX Configurator-DP
GX Configurator-DP Version 7.00A cannot be used.
Upgrade the GX Configurator-DP Version 7.00A to Version
No
7.01B or later. (Please consult your local Mitsubishi
representative.)
No
Set the DP-Master to "QJ71PB92D" in the "Change Master
Type" window in GX Configurator-DP.
1) Check the settings in the "Transfer Setup" window.
No
2) Check the "Starting I/O number" setting in the "Master
Settings" window.
1) Set 9244
for Switch 2 of the intelligent function module
H
No
switches in GX Works2.
2) Write the PLC parameters to the QCPU.
3) Reset the QCPU, or power it OFF and then ON.
9
9
- 5