Mitsubishi Electric Melsec Q Series User Manual page 109

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3) Tp [ms] value
Tp = {(2 + 2 + 4 + 2)
= 38.1 [ms]
4) Scan [ms] value
Scan = 5 [ms]
5) Nand value
Nand = 3
From the above 1) to 4), Tscu [ms] is:
Tscu = TcpuA + Tsw + Tp + Scan
= 8 + 21.567 + 38.1 + 5
= 77.667 [ms]
Therefore, the redundant system switching time, Tsca [ms], is:
Tsca = Tscu + Nand
20
= 77.667 + 3
20
= 137.667 [ms]
3.5 Processing Time
3.5.3 System switching time in redundant system
0.01} + (3
1.0) + 35
2
2
1
2
3
4
5
6
7
8
3
- 68