ABB i-bus KNX Product Manual page 82

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
Dimming to basis brightness
Options:
This parameter defines the brightness value after the staircase lighting time has timed out. It is the bright-
ness value set after the dimming down time (pre-warning phase). The basis brightness hold time as well
as the time for dimming down after light on (Warning before light turned off) is programmable in the
Parameter window - Gx Staircase lighting
Example
A typical application for a basis brightness is for example, in nursing homes or residential care homes in
hallways, where the lighting is never fully switched off. A basis brightness of approx. 20 % should
always exist. If a patient enters the area, it should be illuminated for a certain time (staircase lighting
time) with maximum brightness (100 %).
If function staircase light is active
(running): Behaviour on ...
Brightness value
Options:
With activated function Staircase lighting, the parameter can be used to define the reaction to a
brightness value telegram.
With activated function Staircase lighting, the parameter can be used to define the reaction to dim-
ming telegram to the communication object Relative dimming.
80 2CDC 507 114 D0201 | DGN/S 1.16.1
100 % (255)
...
30 % (77)
...
0 % (OFF)
no reaction
set function in standby
no reaction: A brightness value telegram is ignored.
set function in standby: A brightness telegram ends function Staircase lighting, and the DGN/S
carries out the brightness telegram via the communication object Brightness value. The func-
tion Staircase lighting is latent and waits until a renewed activation via the communication ob-
ject function Activate fct. Staircase lighting or via an ON telegram to the communication object
Switch.
Relative dimming
Options:
no reaction
set function in standby
no reaction: A dimming telegram is ignored.
set function in standby: A dimming telegram ends function Staircase lighting, and the DGN/S
carries out the dimming telegram. The function Staircase lighting is latent and waits until a re-
newed activation via the communication object function Activate fct. Staircase lighting or via an
ON telegram to the communication object Switch.
on page 90.

Advertisement

Table of Contents
loading