ABB i-bus KNX Product Manual page 111

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
21
This communication object is enabled if in the
4 Byte is parameterized with the option yes.
This communication object consists of 4 bytes. The individual bytes contain the number of faults on the entire DALI output.
The following numbering applies for the following list:
High byte
31
2
2
15
2
2
The bit number is identical with the exponent of the bit, e.g. number 2 complies with 2
Bit 0...5
Bit 6
Bit 7
Bit 8...13
Bit 14
Bit 15
Bit 16...21
Bit 22
Bit 23
Bit 24...29
Bit 30
Bit 31
The telegrams are sent immediately after detection of the fault. Should several faults occur at the same time, the telegrams
are sent consecutively on the KNX. If a fault is remedied, this is also reported in the communication object.
Note: The detection of the fault state can take up to 90 seconds, depending on the situation.
22
This communication object is enabled if in the
enable encoded fault message is set with yes:
Using this communication object, the number of groups or individual DALI devices are displayed, which have at least one lamp
or ballast fault (with a converter we refer to a converter fault). The value relates to the lighting group or the individual DALI
device in dependence on the group-orientated or device-based parameterization.
Telegram value:
If there is a ballast fault, this is not simultaneously reported as a lamp fault.
Function
Number of faults statistic
30
29
28
27
26
25
24
2
2
2
2
2
2
14
13
12
11
10
9
8
2
2
2
2
2
2
= number of ballasts in the output (without emergency lighting converter)
= 0, without function
= 0, without function
= number of emergency lighting converters on the output (without ballasts)
= 0, without function
= 0 = all emergency lighting converters are ok
= 1 = at least one emergency lighting converter is defective
= number of lamp faults on the output
= 0 = all emergency lights do not have a fault
= 1 = at least one emergency light has a lamp fault
= 0 = all normal lights are ok
= 1 = at least one normal light has a lamp fault
= number of malfunctioning DALI devices on the output (without ballasts and emergency lighting
converters)
= 0 = all emergency lights do not have a ballast fault
= 1 = at least one emergency light has a ballast fault
= 0 = all normal lights do not have a ballast fault
= 1 = at least one normal light has a ballast fault
Number of faults
0...16 = number of lighting groups with fault
0...64 = number of individual DALI devices (ballast or converter) with fault
Communication object name
DALI output
Parameter window -
Status, page 42, the parameter "Number of faults statistic"
Low byte
23
22
21
20
19
18
2
2
2
2
2
2
7
6
5
4
3
2
2
2
2
2
2
2
DALI output
Parameter window -
Status, page 42, the parameter "Fault group/device" 1 Byte
Data type
Flags
4 byte
C, R, T
non DPT
17
16
2
2
1
0
2
2
2
.
1 byte
C, R, T
DPT 5.010
DGN/S 1.16.1 | 2CDC 507 114 D0201 109