ABB i-bus KNX Product Manual page 51

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
For further information see:
"Coded faults" 2 byte
(ballast/lamp/converter)
Options:
yes
no
Using this communication object (no. 20), the status of a fault for a lighting group or a DALI device
is sent or read in the coded 2 byte communication object Status fault coded.
yes: The communication object Status fault coded is enabled. As soon as a ballast, lamp or
emergency lighting converter fault has occurred in the set group or DALI device, this is indi-
cated in the corresponding bit by the value 1.
no: The communication object Status fault coded is not enabled.
Communication object no.
With the option yes, two further parameters appear:
send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
"Number of faults statistic" 4 byte
Options:
yes
no
Using this coded 4 byte communication object (no. 21), the number of ballasts, lamps and emer-
gency lighting converters can be sent or read.
yes: The coded 4 byte communication object Number of faults statistic (no. 21) is enabled. As
soon as the number of faults on the output changes, this is indicated via this coded communi-
cation object Number of faults statistic (no. 21).
no: The communication object Number of faults statistic is not enabled.
With the option yes, two further parameters appear:
send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
20, page 108.