ABB i-bus KNX Product Manual page 32

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
"Fault gateway supply voltage" 1 bit
Option:
30 2CDC 507 114 D0201 | DGN/S 1.16.1
yes
no
no: Failure of the gateway supply voltage is not reported to the KNX.
yes: The communication object Fault gateway supply is enabled. As soon as the device supply
voltage is interrupted, the communication object Fault gateway supply sends a telegram with
the value 1 on the KNX. The time, at which a telegram is sent, can be adjusted using the fol-
lowing parameters.
send object value
Options:
after a change
after request
after a change or request
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
"Request status values" 1 Bit
Option:
yes
no
Via this communication object, all status messages can be requested, provided that they have been
parameterized with the option after a change or request or only after request.
yes: The 1 bit communication object Request status values is enabled. A further parameter ap-
pears:
Request with object value
Options:
0
1
0 or 1
0: Sending status messages is requested with the value 0.
1: Sending status messages is requested with the value 1.
0 or 1: Sending status messages is requested with the value 0 or 1.