ABB i-bus
KNX
Commissioning
3.2.6
Parameter window Emergency Converter
The emergency lighting converters can be parameterized all together, individually or as common groups of
up to eight emergency lighting converters. This enhances the overview in the ETS and reduces the
parameterization effort. They are disconnected in groups of up to eight emergency lighting converters.
Converter 1...64 parameterisation
Options:
global: All emergency lighting converters 1...64 have the same parameterization properties, which are
to be set in the parameter window C1...C64 Converter.
individual: Parameter window Cx...Cy Converter or Cx Converter for groups or individual parameteri-
zation are available, for a group of emergency lighting converters, of if required, for every individual
emergency lighting converter.
Parameter for automatic emergency tests:
The trigger of tests between two
neighbour emergency converters
have an offset of
x15 min. [0...255]
Options:
This parameter determines an offset interval of 15 minutes, which is used by two neighbouring emergency
converters for automatic testing. The formula used for the offset is the formula DALI short address multi-
plied with the offset. Converter 1 has an offset of 15 minutes, converter 2 has an offset of 30 minutes etc.,
if a delay of 1 (= 15 minutes) is parameterized.
90 2CDC 507 114 D0201 | DGN/S 1.16.1
global
individual
0, 1...255