Commissioning - ABB i-bus KNX Product Manual

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX

Commissioning

3
Commissioning
The parameterization of the DGN/S is implemented with the application program Switch Dim Emergency 1f
DALI/1 and the Engineering Tool Software ETS.
The application program can be found in the ETS at ABB/Lighting/DALI.
The following work must be carried out:
Assignment of the physical KNX device address (ETS)
Optional re-addressing of the DALI devices (DALI-Software-Tool)
Assignment of the DALI devices to lighting groups represented in the KNX. Assignment is undertaken
using the DALI-Software-Tool.
Parameterization of the DGN/S (ETS)
For parameterization purposes, a PC or Laptop with ETS3 or higher and a connection to the KNX, e.g. via
RS232, USB or IP interface, is required.
The DGN/S allocates each connected DALI device, which does not have a DALI address, with the first free
DALI address. This automatic addressing can be prevented using a parameter in the ETS, see
window
also possible with the DALI-Software-Tool without using the ETS, whereby the DALI devices must already
have a DALI address (0...63).
Note
The DGN/S can only control the lamps, which have a DALI address and that are assigned to a lamp
group. The only exception is with manual control, which is activated using the button
the device. In test mode, all DALI devices are switched, irrespective of whether they are assigned with a
DALI address or assigned to a lighting group.
General, page 27. Readdressing of the DALI devices and the assignment to any lighting group is
Parameter
on the front of
DGN/S 1.16.1 | 2CDC 507 114 D0201 21