Commissioning
Enable function scenes 1 bit / 8 bit
Option:
This parameter enables the function Scenes and the corresponding parameter window Scenes. Up to 14
scenes are enabled here. Each of these 14 lighting scenes can be assigned to any of the 16 lighting
groups.
Note
Generally, 16 scenes are available with DALI applications. Scenes 15 and 16 are, however, reserved for
internal applications in the DGN/S.
yes: The parameter window Scenes is enabled.
Enable sequence time curve
(one curve per gateway)
Option:
The DGN/S offers the possibility of allowing a sequence to be run. A sequence is a string of up to a maxi-
mum of ten scenes, which are recalled successively. In this way, it is possible to program running lights us-
ing the DGN/S without additional logic or timer modules.
Note
Only one sequence can be programmed on the DGN/S. The setting is undertaken in the
window
lighting groups which are members. This parameterization is undertaken in
Gx
Group, page 51.
For further information see: Sequence, page 142
yes: The parameter window Sequence is enabled.
yes
no
yes
no
Sequence, page 87. The sequence is recalled by the communication object Switch of the
Parameter
Parameter window
DGN/S 1.16.1 | 2CDC 507 114 D0201 31