3.3.6

Communication objects Converter x

As soon as in parameter window Cx Converter an emergency lighting test is enabled, the communication
object Emergency test trigger for converter x is enabled. The following emergency lighting tests can be
triggered via this communication object for the emergency lighting converter.
Function test
Partial duration test
Duration test
Battery
Explanations about the tests can be found in section 1.3.2.
Via the parameter Enable coded status emergency test in
the communication object for the Emergency test trigger/status changes. Using this communication object,
the result of the emergency lighting test for the emergency lighting converter is transferred on the KNX.
No.
168
This communication object is enabled if in
trigger is set with the option yes.
An emergency lighting test can be triggered via this communication object for the emergency lighting converter x.
The following numbering applies for the following list:
7
2
The bit number is identical with the exponent of the bit, e.g. number 2 complies with 2
Bit 0 ... 2
Bit 3...7
If a new test is requested on the communication object, before the ongoing test has ended, this is immediately interrupted and
the new test is required. This is also the case when the ongoing test is requested again. Only one test can be undertaken on
the converter at any time.
122 2CDC 507 114 D0201 | DGN/S 1.16.1
Function
Emergency test trigger
6
5
4
3
2
1
2
2
2
2
2
2
2
= 000, stops the tests currently in operation
= 001, function test is requested
= 010, partial duration test is requested
= 011, duration test is requested
= 100, battery is requested
= 101, 110 and 111 without function or the evaluation of the request is not considered
= 0 without function or the evaluation of the request is not considered.