ABB i-bus KNX Product Manual page 127

Dali gateway emergency lighting
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
No.
240...246
This communication object is enabled if in
A telegram, which is received via this communication object from the DGN/S, causes the DGN/S to save the current bright-
ness values of the lighting group, which are part of the scene as new scene brightness values for the scene, and to write in the
corresponding lighting groups of the devices. The saved scene values received via the ETS during a download are overwritten
and are lost.
Telegram value:
The scene that is set manually once via the KNX can be protected against overwriting with a download by setting the option no
for Overwrite scene on download in the
ized in the ETS are not written into the DALI devices of the lighting group. The scene brightness values set manually via the
KNX are retained.
Note
Not all 16 lighting groups are considered when saving. Only the lighting groups, which belong to the scene, are
considered.
Thus, for example, the lamp groups in adjacent rooms, which are not part of the scene, are not changed.
Function
Store scene
Parameter window
0 = saving of the scene brightness values of the first scene no. (x)
1 = saving of the scene brightness values of the second scene no. (y)
Parameter window Scene
Communication object name
Scenes x/y
X=1, 3...13
y=2, 4...12
Scenes, page 84, the respective scenes have been enabled.
x, page 85. In this case, the brightness values parameter-
DGN/S 1.16.1 | 2CDC 507 114 D0201 125
Data type
Flags
1 bit
C, W
DPT 1.022