Communications Modules; Available Versamax Plc Communications Modules; Profibus-Dp Network Slave Module - GE VersaMax PLC User Manual

Table of Contents

Advertisement

1.7 Communications Modules

VersaMax PLC CPU
Introduction
For public disclosure
Communications modules provide additional flexibility for VersaMax systems.
These communications modules install on a VersaMax Communications Carrier. Power
for the communications module comes from the main system power supply or from a
booster supply as shown below.
power supply
1.7.1 Available VersaMax PLC Communications
Modules
The following VersaMax PLC communications modules are available:
Communications Modules

Profibus-DP Network Slave Module

DeviceNet Network Control Module
Asi Network Master Module
Serial Communications Module
Communications Carrier
For information about the Communications Carrier, refer to the VersaMax Modules,
Power Supplies, and Carriers User Manual (GFK- 1504).
1.7.2 Profibus-DP Network Slave Module
The Profibus-DP Network Slave Module (IC200BEM002) is a communications module
that exchanges PLC reference table data on the Profibus network. The VersaMax PLC
CPU can read and write this data as though it were conventional bit- and word-type I/O
data.
Multiple Profibus-DP Network Slave Modules may be used in the same VersaMax PLC.
Each one can read up to 244 bytes of data from the network, and send up to 244 bytes of
output data. The total amount of combined inputs and outputs is 384 bytes.
For information about the Profibus-DP Network Slave Module, refer to the VersaMax
System Profibus Network Modules User Manual (GFK-1534, revision A or later).
Profibus Network
Optional booster
Slave Module
power supply
GFK-1503E User Manual 29
IC200BEM002
IC200BEM103
IC200BEM104
IC200CMM020
IC200CHS006

Hide quick links: