14.4 PID Algorithm Selection (PIDISA or PIDIND) and Gain
Calculations
Error Term Sign
SP
+/-
-/+
Deriv Action
PV
284
GFK-1503E
For public disclosure
The PID function supports both the Independent Term (PID_IND) and ISA standard
(PID_ISA) forms of the PID algorithm. The Independent Term form takes its name from
the fact that the coefficients for the proportional, integral and derivative terms act
independently. The ISA algorithm is named for the Instrument Society of America (now
the International Society for Measurement and Control), which standardized and
promoted it.
The two algorithms differ in how words 6 through 8 of the reference array are used and in
how the PID output (CV) is calculated.
The Independent term PID (PID_IND) algorithm calculates the output as:
PID Output = Kp * Error + Ki * Error * dt + Kd * Derivative + CV Bias
where Kp is the proportional gain, Ki is the integral rate, Kd is the derivative time, and dt
is the time interval since the last solution.
The ISA (PID_ISA) algorithm has different coefficients for the terms:
PID Output = Kc * (Error + Error * dt/Ti + Td * Derivative) + CV Bias
where Kc is the controller gain, Ti is the Integral time and Td is the Derivative time. The
advantage of PID_ISA is that adjusting Kc changes the contribution for the integral and
derivative terms as well as the proportional term, which can simplify loop tuning.
If you have the PID_ISA Kc, Ti and Td values, use the following equations to convert
them to use as:PID_IND parameters:
Kp = Kc, Ki = Kc/Ti, and Kd = Kc * Td
The following diagram shows how the PID_IND algorithm works:
Proportional Term =
Kp * Error
Integral Term =
Dead
Previous Integ. Term +
Band
Ki * Error * Time
Derivative Term =
Value
Value
Time
Kd *
Time
The ISA Algorithm (PID_ISA) is similar except that its Kc gain coefficient is applied
after the three terms are summed, so that the integral gain is Kc / Ti and the derivative
gain is Kc * Td.
Bits 0, 1 and 2 in the Config Word set the Error sign, Output Polarity and Derivative
Action, respectively.

14.4.1 Error Term

Both PID algorithms calculate the Error term as
Error = (SP – PV),
which can be changed to Reverse Acting mode:
Error = (PV – SP)
by setting the Error Term mode (bit 0) in the Config Word – (word 13 of the reference
array) to 1.
Reverse -Acting mode is used if you want the CV output to move in the opposite direction
from PV input changes (CV down for PV up) instead of the normal CV up for PV up.
Slew
Upper / Lower
+
Limit
Clamp
CV
Bias
Polarity
CV