3.5 Ethernet LAN Port

3.6 Mode Switch

CPU Module Datasheet: CPUE05
For public disclosure
The Ethernet LAN port supports SRTP Server and Ethernet Global Data. This port
connects directly to a 10BaseT (twisted pair shielded) network without an external
transceiver. The 10BaseT twisted pair shielded cables must meet applicable IEEE 802
standards. CPUE05 automatically selects either half-duplex or full duplex operation, as
sensed from the network connection.
A space is provided on the front of the CPUE05 module where the configured IP Address
can be written.
IP Address
Writable Area
Ethernet
LAN Port
The Mode switch is located behind the module door. It can be used to place the PLC in
Stop or Run mode. It can also be used to block accidental writing to CPU memory and
forcing or overriding discrete data. Use of this feature is configurable. The default
configuration enables Run/Stop mode selection and disables memory protection.