After successful power-up, the STAT LED turns ON on the Ethernet side. Then the
STAT LED should be green for a brief moment. The LAN LED turns ON when it is
connected to the network and blinks when there is traffic. The LAN LED remains
OFF if the module is not connected to the network.
3.
If the STAT LED is amber, check the PLC Fault Table. With the Station Manager
feature, you can also use the LOG command as explained in the VersaMax PLC
Ethernet Station Manager Manual ( GFK-1876).
If a problem occurs during power-up, the Ethernet interface may not begin operating.
Check the Ethernet LEDs, as explained on the following table.
Indications
Off
Hardware failure mode. STAT: Blinks
2-digit error code:
unexpected interrupt
1 – 2
1 – 3
timer failure
1 – 4
DMA failure
2 – 1
RAM failure
2 – 2
stack error
shared memory
2 – 3
interface error
2 – 4
firmware CRC error
unidentified
instruction, or divide
1-Mar
by 0
unexpected SWI
3 – 2
interrupt
prefetch abort error
3 – 3
4-Mar
data abort error
unexpected IRQ
3 – 5
request
unexpected FIQ
3 – 6
interrupt
reserved exception
7-Mar
error
fatal operating
1-Apr
system startup or
EEPROM error
Actions
Make sure the PLC has power
Look in the PLC Fault Table for problems
Recheck configuration
Check module installation
If the problem persists, replace PLC CPU
Note error code
Power cycle or restart Ethernet interface
If problem persists, replace the PLC
hardware.