Installing An Expansion Transmitter Module; Removing An Expansion Transmitter Module - GE VersaMax PLC User Manual

Table of Contents

Advertisement

4.2 Installing an Expansion Transmitter Module

54
GFK-1503E
For public disclosure
If the VersaMax PLC will have more than one expansion rack or one expansion rack that
uses an Isolated Expansion Receiver Module (IC200ERM001) as its interface to the
expansion bus, an Expansion Transmitter Module must be installed to the left of the CPU.
The Expansion Transmitter Module must be installed on the same section of DIN rail as
the rest of the modules in the main rack (rack 0).
Expansion Transmitter Module
CPU and Power Supply
ETM
PS
CPU
VersaMax PLC Main Rack (0)
1.
Make sure rack power is off.
2.
Attach the Expansion Transmitter to DIN rail to the left of the CPU position.
Install the CPU. Connect the modules and press them together until the connectors
3.
are mated.
4.
After completing any additional system installation steps, apply power and observe
the module LEDs.
On indicates presence of 5VDC power.
Off indicates no 5VDC power.
Blinking or On indicates active
communications on expansion bus.
Off indicates no communications.

4.2.1 Removing an Expansion Transmitter Module

1.
Make sure rack power is off.
2.
Slide module on DIN rail away from the CPU in the main rack.
3.
Using a small screwdriver, pull down on the tab on the bottom of the module and lift
the module off the DIN rail.
VersaMax PLC User Manual