GE VersaMax PLC User Manual page 62

Table of Contents

Advertisement

Pin
Signal
1
n/c
2
TXD
3
RXD
4
n/c
5
GND
6
n/c
7
CTS
8
RTS
9
n/c
Shell
SHLD
1
6
2
7
3
8
4
9
5
The shield must connect to
shell of connectors on both
ends of the cable.
62
GFK-1503E
For public disclosure
4.7.3 Port 1: RS-232
4.7.3.1 Pin Assignments for Port 1
Port 1 is an RS-232 port with a 9-pin female D-sub connector. It is used as the boot loader
port for upgrading the CPU firmware. The pinout of Port 1 allows a simple
straight-through cable to connect with a standard AT-style RS-232 port. Cable shielding
attaches to the shell.
Direction
Function
Output
Transmit Data output
Input
Receive Data input
0V/GND signal reference
Input
Clear to Send input
Output
Request to Send output
Cable Shield wire connection / 100% (Continuous) shielding
cable shield connection
4.7.3.2 RS-232 Point-to-Point Connection
In point-to-point configuration, two devices are connected to the same communication
line. For RS-232, the maximum length is 15 meters (50ft).
1
6
2
7
3
8
4
9
5
PC 9-Pin
CPU
Serial Port
Port 1
9-pin female
9-pin male
(2) RXD
(2) TXD
(3) TXD
(3) RXD
(5) GND
(5) GND
(7) RTS
(7) CTS
(8) CTS
(8) RTS
VersaMax PLC User Manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents