98

Complete parameter descriptions

This section describes the actual signals and parameters for ACS550.
Group 99: START-UP DATA
This group defines special start-up data required to:
• set up the drive
• enter motor information.
Code Description
9901 LANGUAGE
Selects the display language. There are two different Assistant Control Panels, each supporting a different language
set. (Panel ACS-CP-L supporting languages 0, 2, 11...15 will be integrated into ACS-CP-A.)
Assistant Control Panel ACS-CP-A:
0 =
ENGLISH
5 =
PORTUGUES
10 =
SVENSKA
15 =
MAGYAR
Assistant Control Panel ACS-CP-D (Asia):
0 =
ENGLISH
9902 APPLIC MACRO
Selects an application macro. Application macros automatically edit parameters to configure the ACS550 for a
particular application.
1 =
ABB STANDARD
6 =
PID CONTROL
0 =
1
USER S
LOAD
31 =
– FlashDrop parameter values as defined by the FlashDrop file. Parameter view is selected by
LOAD FD SET
parameter 1611
PARAMETER VIEW
• FlashDrop is an optional device for fast copying of parameters to unpowered drives. FlashDrop allows easy
customization of the parameter list, e.g. selected parameters can be hidden. For more information, see MFDT-01
FlashDrop User's Manual [3AFE68591074 (English)].
-1 =
1
, -3 =
USER S
SAVE
drive permanent memory for later use. Each set contains parameter settings, including
DATA, and the results of the motor identification run.
0 =
1
, -2 =
USER S
LOAD
9904 MOTOR CTRL MODE
Selects the motor control mode.
1 =
:
– sensorless vector control mode.
VECTOR
SPEED
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
, or 2001
MAXIMUM SPEED
speed).
2 =
:
.
VECTOR
TORQ
• Reference 1 is speed reference in rpm.
• Reference 2 is torque reference in % (100% is nominal torque.)
3 =
:
– scalar control mode.
SCALAR
FREQ
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM FREQ
maximum speed).
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
• Must equal the value on the motor rating plate.
• The ACS550 cannot supply the motor with a voltage greater than the input power (mains) voltage.
Parameters
1 =
(
)
2 =
ENGLISH
AM
6 =
7 =
NEDERLANDS
11 =
12 =
RUSSKI
1 =
2 =
CHINESE
2 = 3-
3 =
WIRE
7 =
8 =
PFC CONTROL
-1 =
1
-2 =
USER S
SAVE
.
2
– With these it is possible to save two different user parameter sets into the
USER S
SAVE
2
– With these the user parameter sets can be taken back in use.
USER S
LOAD
if the absolute value of the minimum speed is greater than the maximum
MINIMUM SPEED
, or 2007
if the absolute value of the minimum speed is greater than the
MINIMUM FREQ
3 =
DEUTSCH
ITALIANO
8 =
FRANÇAIS
DANSK
13 =
POLSKI
TÜRKÇE
3 =
KOREAN
JAPANESE
4 =
ALTERNATE
MOTOR POT
31 =
TORQUE CTRL
LOAD FD SET
2
-3 =
USER S
LOAD
USER S
ACS550 User's Manual
4 =
ESPAÑOL
9 =
SUOMI
14 =
CZECH
5 =
/
HAND
AUTO
2
SAVE
Group 99: START-UP