ACS550 User's Manual
Alarm
code
2004
2005
2006
2007
2008
2009
2010
2011
2012
Display
The change in direction being attempted is not allowed. Either:
DIR LOCK
• Do not attempt to change the direction of motor rotation, or
• Change parameter 1003
reverse operation is safe).
Fieldbus communication has timed out. Check for and correct:
IO COMM
• Fault setup (3018
• Communication settings
Group 53: EFB PROTOCOL
• Poor connections and/or noise on line.
1
Analog input 1 is lost, or value is less than the minimum setting.
AI
LOSS
Check:
• Input source and connections.
• Parameter that sets the minimum (3021).
• Parameter that sets the alarm/fault operation (3001),
2
Analog input 2 is lost, or value is less than the minimum setting.
AI
LOSS
Check:
• Input source and connections.
• Parameter that sets the minimum (3022).
• Parameter that sets the alarm/fault operation (3001).
Panel communication is lost and either:
PANEL LOSS
• Drive is in local control mode (the control panel displays LOC), or
• Drive is in remote control mode (REM) and is parameterized to
accept start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections.
• Parameter 3002
• Parameters in
REFERENCE SELECT
Drive heatsink is hot. This alarm warns that a
DEVICE
may be near.
OVERTEMP
R1...R4 & R7/R8: 100 °C (212 °F)
R5/R6: 110 °C (230 °F)
Check for and correct:
• Fan failure.
• Obstructions in the air flow.
• Dirt or dust coating on the heat sink.
• Excessive ambient temperature.
• Excessive motor load.
Motor is hot, based on either the drive's estimate or on temperature
MOTOR TEMP
feedback. This alarm warns that a
near. Check:
• Check for overloaded motor.
• Adjust the parameters used for the estimate (3005...3009).
• Check the temperature sensors and
MEAS.
Not used.
RESERVED
Motor is operating in the stall region. This alarm warns that a
MOTOR STALL
fault trip may be near.
STALL
Description
to allow direction change (if
DIRECTION
and 3019
COMM FAULT FUNC
(Group 51: EXT COMM MODULE
as appropriate).
.
PANEL COMM ERR
Group 10: START/STOP/DIR
(if drive operation is REM).
MOT OVERTEMP
Group 35: MOTOR TEMP
251
).
COMM FAULT TIME
or
and
Group 11:
fault
DEVICE OVERTEMP
fault trip may be
MOTOR
Diagnostics