Complete Parameter Descriptions

This section describes the actual signals and parameters for ACS550.

Group 99: Start-up Data

This group defines special Start-up data required to:
• Set up the drive.
• Enter motor information.
Code Description
9902 APPLIC MACRO
Selects an application macro. Application macros automatically edit parameters to configure the ACS550 for a
particular application.
1 =
ABB STANDARD
6 =
PID CONTROL
11 =
2
USER S
LOAD
9904 MOTOR CTRL MODE
Selects the motor control mode.
1 = s
PEED CONTROL
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum speed, equal to the value of parameter 2002
, or 2001
MAXIMUM SPEED
speed).
2 =
TORQUE CONTROL
• Reference 1 is speed reference in rpm.
• Reference 2 is torque reference in % (100% is nominal torque.)
3 =
SCALAR CONTROL
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute maximum frequency, equal to the value of parameter
2008
MAXIMUM FREQUENCY
than the maximum speed).
9905 MOTOR NOM VOLT
Defines the nominal motor voltage.
• Must equal the value on the motor rating plate.
• Sets the maximum drive output voltage supplied to the motor.
• The ACS550 cannot supply the motor with a voltage greater than the
mains voltage.
9906 MOTOR NOM CURR
Defines the nominal motor current.
• Must equal the value on the motor rating plate.
• Range allowed: (0.2...2.0) · I
9907 MOTOR NOM FREQ
Defines the nominal motor frequency (field weakening point).
• Range: 10...500 Hz (typically 50 or 60 Hz)
• Sets the frequency at which output voltage equals the
.
VOLT
9908 MOTOR NOM SPEED
Defines the nominal motor speed.
• Must equal the value on the motor rating plate.
9909 MOTOR NOM POWER
Defines the nominal motor power.
• Must equal the value on the motor rating plate.
Start-Up
2 = 3-
WIRE
7 =
PFC CONTROL
12 =
2
USER S
SAVE
– sensorless vector control mode.
if the absolute value of the minimum speed is greater than the maximum
MINIMUM SPEED
.
– scalar control mode.
, or 2007
MINIMUM FREQUENCY
(where I
is drive current).
N
N
3 =
4 =
ALTERNATE
MOTOR POT
8 =
9 =
TORQUE CTRL
USER S
if the absolute value of the minimum speed is greater
MOTOR NOM
ACS550 User's Manual
5 =
/
HAND
AUTO
1
10 =
LOAD
USER S
Output voltage
P 9905
P 9907
1
SAVE
Output
frequency