ACS550 User's Manual
Select the application macro (parameter 9902). The general
parameter setting procedure is given above.
The default value 1 (
Select the motor control mode (parameter 9904).
1 (
:
) is suitable in most cases. 2 (
VECTOR
SPEED
torque control applications. 3 (
• for multimotor drives when the number of the motors connected to the
drive is variable
• when the nominal current of the motor is less than 20% of the nominal
current of the drive
• when the drive is used for test purposes with no motor connected.
Enter the motor data from the motor nameplate:
3
motor
V
690 Y
400 D
660 Y
380 D
415 D
440 D
Cat. no
6312/C3
• motor nominal voltage (parameter 9905)
• motor nominal current (parameter 9906)
Allowed range: 0.2...2.0 · I
• motor nominal frequency (parameter 9907)
• motor nominal speed (parameter 9908)
• motor nominal power (parameter 9909)
) is suitable in most cases.
ABB STANDARD
:
) is recommended
SCALAR
FREQ
ABB Motors
M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F
IP 55
IA/IN t E/s
Hz
kW
r/min
A
cos
50
30
1475
32.5
0.83
50
1475
56
0.83
30
50
30
1470
34
0.83
30
1470
59
0.83
50
1475
50
30
54
0.83
35
1770
59
0.83
60
3GAA 202 001 - ADA
6210/C3
IEC 34-1
A
2hd
:
) is suitable for
VECTOR
TORQ
380 V
supply
voltage
180
9902
REM
PAR
9904
REM
PAR
Note: Set the motor data to
exactly the same value as on
the motor nameplate. For
example, if the motor nominal
speed is 1470 rpm on the
nameplate, setting the value of
parameter
9908
MOTOR NOM
to 1500 rpm results in the
SPEED
wrong operation of the drive.
9905
REM
PAR
9906
REM
PAR
9907
REM
PAR
9908
REM
PAR
9909
REM
PAR
Start-up, control with I/O and ID Run
33
FWD
FWD
FWD
FWD
FWD
FWD
FWD