Avg. braking power –
overhauling load
Avg. braking power
during deceleration
to zero
The many variables in the last requirement above are most easily dealt with using
the following tables.
• First, determine your maximum braking time ON (ON
OFF (OFF
• Calculate duty cycle:
• In the appropriate table, find the column that best matches your data:
– ON
– Duty cycle < column specification
• Find the row that matches your drive.
• The minimum power rating for deceleration to zero is the value in the selected
row/column.
• For overhauling loads, double the rating in the selected row/column, or use the
"Continuous ON" column.
208...240 V drives
Type code
ACS550-
01/U1-
see below
Three-phase supply voltage, 208...240 V
-04A6-2
-06A6-2
-07A5-2
-012A-2
-017A-2
-024A-2
-031A-2
1
Resistor time constant specification must be > 85 seconds.
Technical data
Power
Temperature
2x
x
) and load type (deceleration or overhauling load).
MIN
ON
MAX
=
Duty cycle
(ON
+ OFF
MAX
< column specification and
MAX
Resistance
P
r3
< 3 s ON
R
R
MAX
MIN
> 27 s OFF
< 10% Duty
ohm
ohm
W
234
80
45
160
80
65
117
44
85
80
44
125
48
44
210
32
30
315
23
22
430
Deceleration curve
MAX
· 100%
)
MIN
1
Resistor
minimum continuous power rating
Deceleration-to-zero rating
P
P
r10
r30
< 10 s ON
< 30 s ON
> 50 s OFF
> 180 s OFF
< 17% Duty
< 14% Duty
W
W
80
120
120
175
160
235
235
345
390
575
590
860
800
1175
ACS550 User's Manual
Overhauling load
curve
Time
Time
), minimum braking time
P
rcont
P
Continuous ON
r60
> 60 s ON
< 60 s ON
> 180 s OFF
> 25% Duty
< 25% Duty
W
W
200
1100
280
1500
390
2200
570
3000
950
4000
1425
5500
1940
7500

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-01Acs550-u1

Table of Contents