102
Code Description
0136 COMM VALUE 2
Free data location that can be written from serial link.
0137 PROCESS VAR 1
Process variable 1
• Defined by parameters in
0138 PROCESS VAR 2
Process variable 2
• Defined by parameters in
0139 PROCESS VAR 3
Process variable 3
• Defined by parameters in
0140 RUN TIME
The drive's accumulated running time in thousands of hours (kh).
• Cannot be reset.
0141 MWH COUNTER
The drive's accumulated power consumption in megawatt hours.
• Cannot be reset.
0142 REVOLUTION CNTR
The motor's accumulated revolutions in millions of revolutions.
• Can be reset by pressing UP and DOWN keys simultaneously when the control panel is in the Parameters mode.
0143 DRIVE ON TIME HI
The drive's accumulated power-on time in days.
• Cannot be reset.
0144 DRIVE ON TIME LO
The drive's accumulated power-on time in 2 second ticks (30 ticks = 60 seconds).
• Shown in format hh.mm.ss.
• Cannot be reset.
0145 MOTOR TEMP
Motor temperature in degrees Celsius / PTC resistance in ohms.
• Applies only if motor temperature sensor is set up.
• See parameter 3501.
0146 MECH ANGLE
Defines the motor shaft's angular position to about 0.01° (32,768 divisions for 360°). The position is defined as 0 at
power up.
During operation the zero position can be set by:
• a Z-pulse input, if parameter 5010
• parameter 5011
POSITION RESET
• any status change of parameter 5002
0147 MECH REVS
A signed integer that counts full revolutions of the motor shaft. The value:
• increments when parameter 0146
• decrements when parameter 0146
0148 Z PLS DETECTED
Encoder zero pulse detector. When a Z-pulse defines the zero position, the shaft must pass through the zero position
to trigger a Z-pulse. Until then, the shaft position is unknown (the drive uses the shaft position at power up as zero).
This parameter signals when parameter 0146
power-up and changes to 1 =
• parameter 5010
Z PLS ENABLE
• an encoder Z-pulse has been detected.
0150 CB TEMP
Temperature of the drive control board in degrees Celsius.
Note: Some drives have a control board (OMIO) that does not support this feature. These drives always show the
constant value of 25.0 °C.
Parameters
Group 34: PANEL
DISPLAY.
Group 34: PANEL
DISPLAY.
Group 34: PANEL
DISPLAY.
= 1 (
Z PLS ENABLE
, if parameter 5010
Z PLS ENABLE
ENCODER ENABLE
changes from 32767 to 0
MECH ANGLE
changes from 0 to 32767.
MECH ANGLE
MECH ANGLE
only if:
DETECTED
= 1 (
) and
ENABLE
)
ENABLE
= 2 (
)
DISABLE
.
is valid. The parameter starts at 0 =
ACS550 User's Manual
on
NOT DETECTED