The following table summarizes the 4xxxx drive control registers 40001...40099 (for
4xxxx registers above 40099, see the drive parameter list, e.g. 40102 is parameter
0102):
40001
40002 Reference 1
40003 Reference 2
40004
40005 Actual 1
40006 Actual 2
40007 Actual 3
40008 Actual 4
40009 Actual 5
40010 Actual 6
40011
40012 Actual 8
40031 ACS550
40032 ACS550
40033 ACS550
40034 ACS550
Embedded fieldbus
Modbus register
Access
R/W
CONTROL WORD
R/W
R/W
R
STATUS WORD
R
(select using 5310)
R
(select using 5311)
R
(select using 5312)
R
(select using 5313)
R
(select using 5314)
R
(select using 5315)
Actual 7
R
(select using 5316)
R
(select using 5317)
R/W
CONTROL
LSW
WORD
R
CONTROL
MSW
WORD
R
STATUS
LSW
WORD
R
STATUS
MSW
WORD
Remarks
Maps directly to the profile'
if 5305 = 0 or 2 (ABB Drives profile). Parameter 5319 holds
a copy in hex format.
Range = 0...+20000 (scaled to 0...1105
-20000...0 (scaled to 1105
Range = 0...+10000 (scaled to 0...1108
-10000...0 (scaled to 1108
Maps directly to the profile'
5305 = 0 or 2 (ABB Drives profile). Parameter 5320 holds a
copy in hex format.
By default, stores a copy of 0103
parameter 5310 to select a different actual value for this
register.
By default, stores a copy of 0104
5311 to select a different actual value for this register.
By default, stores nothing. Use parameter 5312 to select an
actual value for this register.
By default, stores nothing. Use parameter 5313 to select an
actual value for this register.
By default, stores nothing. Use parameter 5314 to select an
actual value for this register.
By default, stores nothing. Use parameter 5315 to select an
actual value for this register.
By default, stores nothing. Use parameter 5316 to select an
actual value for this register.
By default, stores nothing. Use parameter 5317 to select an
actual value for this register.
Maps directly to the Least Significant Word of the DCU
profile's
. Supported only if 5305 = 1.
CONTROL WORD
See parameter 0301.
Maps directly to the Most Significant Word of the DCU
profile's
. Supported only if 5305 = 1.
CONTROL WORD
See parameter 0302.
Maps directly to the Least Significant Word of the DCU
profile's
. Supported only if 5305 = 1.
STATUS WORD
See parameter 0303.
Maps directly to the Most Significant Word of the DCU
profile's
. Supported only if 5305 = 1.
STATUS WORD
See parameter 0304.
ACS550 User's Manual
. Supported only
S CONTROL WORD
1
), or
REF
MAX
1
...0).
REF
MAX
2
), or
REF
MAX
2
...0).
REF
MAX
. Supported only if
S STATUS WORD
. Use
OUTPUT FREQ
. Use parameter
CURRENT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-01Acs550-u1

Table of Contents