ABB ACS550 User Manual page 213

Hide thumbs Also See for ACS550:
Table of Contents

Advertisement

ACS550 User's Manual
ABB Drives profile
The following table and the state diagram later in this sub-section describe the
STATUS WORD
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13...
15
content for the ABB Drives profile.
ABB Drives profile (EFB)
Name
Value
RDY_ON
1
0
RDY_RUN
1
0
RDY_REF
1
0
TRIPPED
0...1
0
OFF_2_STA
1
0
OFF_3_STA
1
0
SWC_ON_INHIB
1
0
ALARM
1
0
AT_SETPOINT
1
0
REMOTE
1
0
ABOVE_LIMIT
1
0
EXT CTRL LOC
1
0
EXT RUN ENABLE 1
0
Unused
(See parameter 5320)
STATUS WORD
Description
(Correspond to states/boxes in the state diagram)
READY TO SWITCH ON
NOT READY TO SWITCH ON
READY TO OPERATE
1
OFF
ACTIVE
OPERATION ENABLED
OPERATION INHIBITED
FAULT
No fault
2
OFF
INACTIVE
2
OFF
ACTIVE
3
OFF
INACTIVE
3
OFF
ACTIVE
-
SWITCH
ON INHIBIT ACTIVE
-
SWITCH
ON INHIBIT NOT ACTIVE
Alarm (See section
Alarm listing
alarms.)
No alarm
. Actual value equals (within tolerance limits) the
OPERATING
reference value.
Actual value is outside tolerance limits (not equal to reference
value).
Drive control location:
REMOTE
Drive control location:
LOCAL
Supervised parameter's value > supervision high limit.
Bit remains "1" until supervised parameter's value < supervision
low limit.
See
Group 32:
SUPERVISION.
Supervised parameter's value < supervision low limit.
Bit remains "0" until supervised parameter's value > supervision
high limit.
See
Group 32:
SUPERVISION.
External control location 2 (
External control location 1 (
External Run Enable signal received
No External Run Enable signal received
on page
250
for details on
(
1 or
2)
EXT
EXT
2) selected
EXT
1) selected
EXT
Embedded fieldbus
213

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-01Acs550-u1

Table of Contents