2 Installation and Commissioning, IRC5
2.9.1. Installation of EMC shield
Continued
Procedure
The procedure below details how to install the EMC cage on the Drive Module.
86
Action
1.
DANGER!
Before any work inside the cabinet, please
observe the safety information in section
DANGER - Make sure that the main power
has been switched off! on page
2. Connect the Ethernet cable shield on the
Drive Module.
NOTE!
Both signal and Ethernet cables must be in
good mechanical and electrical contact with
the specified shield plate. The signal cable
might be prepared for shield connection at
delivery but the Ethernet cable is not. In any
case make sure that the isolation is removed
at right lenght for both cables.
WARNING!
Make sure that the internal shield of the cable
is not damaged during the isolation removal.
WARNING!
Both cables are connected to the upper plate.
Make sure that you have extra lenght so that
cable removal before opening the module will
not be necessary.
NOTE!
A tightening torque must be used at 0.5 Nm.
Info/Illustration
26.
xx0600003288
A: shield connection
3HAC027707-001 Revision: D
Continues on next page