(1) Setup on the server computer (database)
The actual performance for every 5 seconds, and fraction defective and operation rate for every hour are
managed using the database.
(a) Table setting
• Table name: PROCESS
• Field:
DATETIME
PERFORMANCE
REJECT
WORKINGRATE
• ODBC setting
ODBC data source name: PROCESS
Driver: OracleHome2
TNS service name: PROCESS
• DB Connection Service setting
Service port No.: 5112
Timeout: 10 seconds
(2) Setup on the configuration computer (GT Designer3)
(a) IP address setting
• Communication Settings
Extend I/F-1: 1
CH No.: *
Driver: Ethernet Download
• Detailed setting
IP address: 192.168.11.101
Ethernet Download: 5014
Default Gateway: 0.0.0.0
Subnet mask: 255.255.255.0
(b) Script
No.
1
2
(c) Screen design
For how to create the screens, refer to the following manual.
GT Designer3 Version1 Screen Design Manual (Fundamentals)
App - 14
Name
Data type
CHAR
NUMBER
NUMBER
NUMBER
Trigger
During M101=ON
When M102 rises
Size
Scale
32
10
0
10
1
10
1
Operation
[w:GD540]=[w:D540];
[w:GD542]=[w:D542];
[b:M101]=0;
[w:GD544]=[w:D544];
[w:GD546]=[w:D546];
[b:GB102]=[b:M102];
[b:M102]=0;
NULL
Default
Possible
Possible
Possible
Possible
Remarks
M101: Operation stop flag
D540: Operation time
D542: Accumulated down time
M102: Completion notification
(The GOT collects PLC information
upon completion of the processing.)