12.5.3 Address switch

L240/BS
Function switch 2-3 "Tamper contact":
Using function switch 2-3, the cover tamper contact on Evaluation Module
L240/BS can be activated or deactivated. The cover tamper contact must be
activated in VdS approved installations.
OFF (standard setting): The cover tamper contact is operational (tamper
monitoring) and triggers a tampering (sabotage) alarm should the cover
be opened.
ON: The cover tamper contact is non- functional and not operational
(e.g. to suppress a tampering alarm during set-up and commissioning).
Opening the cover will not trigger a tampering alarm.
Function switch 2-4 "Test mode":
Using function switch 2-4, the Evaluation Module L240/BS can be operated
in test mode.
OFF: Standard mode
ON: Test mode
During operation, the DIP switch should be set to OFF.
Function switch 2-5:
Must be "OFF".
Using the address switch, the Evaluation Module L240/BS connected to the
XIB security bus is addressed. Each Evaluation Module L240/BS has
(independent of the zone) its own address. The address range for the
Evaluation Module L240/BS commences with "1" and must be successive (1,
2, 3, ... 8).
Up to 8 Evaluation Modules L240/BS can be connected to the Intrusion
Alarm Panel L240.
Evaluation
Switch
module address
3-1
1
OFF
2
ON
3
OFF
4
ON
5
OFF
6
ON
7
OFF
8
ON
Table 1: Addressing
Switch
Switch
Switch
3-2
3-3
3-4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
Switch
3-5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
87