Setpoint Adjustment - Resetting The Manual Adjustment For Change Of Operating Mode; Setpoint Adjustment - Resetting The Manual Adjustment Via Object; Setpoint Adjustment - Permanent Storage Of On-Site Operation; Temperature Reading - Inputs Of Temperature Reading - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Pos: 31.7.110 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — Zurücksetzen der manuellen Verstellung bei Wechsel des Betriebsmodus @ 40\mod_1421743830811_15.docx @ 313769 @ 3 @ 1
11.3.89

Setpoint adjustment - Resetting the manual adjustment for change of operating mode

Options:
If the device switches to a new operating mode, the manual adjustment is deleted and the
parameterized setpoint temperature for the operating mode plus any change by the base
setpoint value object will be applied if this parameter is activated. Example: Comfort
temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. Change to Eco with
programmed temperature 17°C. The device regulates the temperature to 17°C, since the
manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the temperature
in the new operating mode. Example: Comfort temperature of 21°C plus manual adjustment of
1.5°C = 22.5°C. If the system switches to Eco with a parameterized temperature of 17°C, the
device regulates the temperature to 18.5°C, since the manual adjustment is added.
Pos: 31.7.111 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — Zurücksetzen der manuellen Verstellung über Objekt @ 40\mod_1421744043574_15.docx @ 313784 @ 3 @ 1
11.3.90

Setpoint adjustment - Resetting the manual adjustment via object

Options:
If this parameter is activated, a separate object can be used to delete the manual adjustment at
any time. Example of application: Resetting the manual adjustment on all devices located in a
building using a system clock.
Pos: 31.7.112 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwertverstellung — Vorortbedienung dauerhaft speichern @ 40\mod_1421744100048_15.docx @ 313799 @ 3 @ 1
11.3.91

Setpoint adjustment - Permanent storage of on-site operation

Options:
If this parameter is activated, the manual settings for setpoint and, where applicable, fan speed
level, as well as the value of the "Basic load" object, will be stored in the device and re-activated
after a reset. If the device is re-programmed, the stored setpoint values will also be deleted.
Pos: 31.7.113 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Eingänge der Temperaturerfassung @ 40\mod_1421744675480_15.docx @ 313814 @ 3 @ 1
11.3.92

Temperature reading - Inputs of temperature reading

Options:
The room temperature can be measured at the device or fed to the device by an object via the
bus. In addition, weighted measuring is also available, in which the weighted average of up to
three temperature values (1 x internal, 2 x external) is calculated and used as an input value for
control.
Pos: 31.7.114 /Systemmodule/++++++++++++++ Seitenumbruch +++++++++++++++ @ 41\mod_1422789416992_0.docx @ 333487 @ @ 1
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
No
Yes
No
Yes
No
Yes
Internal measurement
External measurement
Weighted measurement
objects
— 60 —

Advertisement

Table of Contents
loading

Table of Contents