Pos: 31.7.130 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Alarmfunktionen — Taupunktalarm @ 40\mod_1421745829394_15.docx @ 314009 @ 3 @ 1
11.3.105 Alarm functions — Dew point alarm
Options:
When refrigerating machines are used, dew may appear on the refrigerant supply lines during
operation as a result of excessive cooling and/or humidity. The dew indicator reports the dew
formation via the "Dew point alarm" object (receiving only). This causes the controller to switch
to a protective mode. This status is indicated by the corresponding icon on devices that have a
display. Local operation is blocked. Operation is only possible again after the alarm has been
deactivated.
Note
This parameter is only available when the "Control function" parameter is set
either on "Cooling", "Cooling with additional stage", "Heating and cooling" or
"Heating and cooling with additional stages".
Pos: 31.7.131 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Alarmfunktionen — Temperatur Frostalarm HVAC- u. RHCC-Status (°C) @ 40\mod_1421745887146_15.docx @ 314024 @ 3 @ 1
11.3.106 Alarm functions - Frost alarm temperature for HVAC and RHCC status (°C)
Options:
The RHCC status and HVAC objects have a frost alarm bit. It the input temperature of the
controller drops below the temperature set in this parameter, then the frost alarm bit is set in the
status objects. It is reset when the temperature is exceeded.
Pos: 31.7.132 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Alarmfunktionen — Temperatur Hitzealarm RHCC-Status (°C) @ 40\mod_1421745946645_15.docx @ 314039 @ 3 @ 1
11.3.107 Alarm functions - Heat alarm temperature for RHCC status (°C)
Options:
The RHCC status object has a heat alarm bit. If the input temperature of the controller exceeds
the temperature set in this parameter, then the heat alarm bit is set in the status object. It is
reset when the temperature falls below the set temperature.
Pos: 31.7.133 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen - Lüfterstufen @ 40\mod_1421746005473_15.docx @ 314054 @ 3 @ 1

11.3.108 Fan coil settings - Fan speed levels

Note
This parameter is only available if the "Device function" parameter is set on either
"Single device" or "Master device" and the "Control value type" parameter is set
on "Fan coil".
Pos: 31.7.134 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen - Lüfterstufen — Anzahl der Lüfterstufen @ 40\mod_1421746070041_15.docx @ 314069 @ 3 @ 1

11.3.109 Fan coil settings - Fan speed levels Number of fan speed levels

Options:
This parameter is used to specify the number of fan speed levels the actuator will use to control
the fan of the fan coil.
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
No
Yes
Setting option between 0 - 15
Setting option between 25 - 70
3 levels
5 levels
objects
— 64 —