Selection of installation site

Pos: 18.6 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Montage und elektrischer Anschluss/KNX/KNX-Sensorik/Millenium/6124 - Raumtemperaturregler/Auswahl des Montageortes @ 26\mod_1343988571510_15.docx @ 226701 @ @ 1
For proper commissioning please observe the following steps:
The room temperature controller should be installed at a
height of approximately 150 cm from the floor and 50 cm from
a door frame.
The room temperature controller should be installed on a wall
opposite a radiator.
The angles of room architecture should not separate a radiator
and the room temperature controller from each other.
Installing a room temperature controller close to a radiator or
behind curtains is not practical.
This equally applies to the installation on an exterior wall - low
outside temperatures have an effect on temperature
regulation.