Setpoint Settings - Hysteresis For Switchover Heating/Cooling (X 0.1°C); Setpoint Settings - Setpoint Temperature For Heating And Cooling Comfort (°C); Setpoint Settings - Setpoint Temperature For Heating Comfort (°C); Setpoint Settings - Reduction For Standby Heating (°C) - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Pos: 31.7.86 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwerteinstellungen — Hysterese für Umschaltung Heizen/Kühlen (x 0,1°C) @ 40\mod_1421741480026_15.docx @ 313484 @ 3 @ 1
11.3.69
Setpoint settings - Hysteresis for switchover heating/cooling (x 0.1°C)
Options:
This parameter specifies the one-sided hysteresis for switching between heating and cooling
when "Setpoint heating comfort = Setpoint cooling comfort" is active. If the room temperature
exceeds the setpoint temperature value plus hysteresis, the system switches to cooling. If the
room temperature falls below the setpoint temperature value minus hysteresis, the system
switches to heating.
Note
This parameter is only available when the "Setpoint heating comfort = Setpoint
cooling comfort" parameter is set on "Yes".
Pos: 31.7.87 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwerteinstellungen — Solltemperatur Komfort Heizen und Kühlen (°C) @ 40\mod_1421741566809_15.docx @ 313499 @ 3 @ 1
11.3.70
Setpoint settings - Setpoint temperature for heating and cooling comfort (°C)
Options:
Specifies the comfort temperature for heating and cooling when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating and cooling" or "heating and cooling with additional stages".
Pos: 31.7.88 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwerteinstellungen — Solltemperatur Komfort Heizen (°C) @ 40\mod_1421741628522_15.docx @ 313514 @ 3 @ 1
11.3.71
Setpoint settings - Setpoint temperature for heating comfort (°C)
Options:
Specifies the comfort temperature for heating when people are present.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating" or "Heating with additional stage".
Pos: 31.7.89 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Sollwerteinstellungen — Absenkung Standby Heizen (°C) @ 40\mod_1421741705524_15.docx @ 313529 @ 3 @ 1
11.3.72
Setpoint settings - Reduction for standby heating (°C)
Options:
Specifies the temperature in heating mode when nobody is present. On devices with a display,
this mode is indicated by the standby icon.
Note
This parameter is only available when the "Control function" parameter is set on
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
Pos: 31.7.90 /Systemmodule/++++++++++++++ Seitenumbruch +++++++++++++++ @ 41\mod_1422789416992_0.docx @ 333487 @ @ 1
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
Setting option between 5 - 100
Setting option between 10 - 40
Setting option between 10 - 40
Setting option between 10 - 40
objects