Heating Control - Heating Type; Heating Control - P-Component (X 0.1°C); Heating Control - I-Component (Min.) - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
11.3.8

Heating control - Heating type

Options:
Multiple heating types (panel heating, convector heating or fan coil) with preset parameters are
available to the user.
If the required heating type is not available, individual parameters can be specified in free
configuration.
Note
This parameter is only available when "Control value type" parameter is set either
on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil".
Pos: 31.7.11 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleRegelung Heizen — P-Anteil (x 0,1°C) @ 40\mod_1421679772900_15.docx @ 312513 @ 3 @ 1
11.3.9
Heating control - P-component (x 0.1°C)
Options:
The P-component refers to the proportional band of a control. It fluctuates around the setpoint
value and can be used to influence control speed with a PI controller. The smaller the setpoint,
the faster it reacts to the control. However, to avoid the risk of an overshoot, this value should
not be set too low. A P-component from 0.1 to 25.5 K can be set.
Note
This parameter is only available when "Control value type" parameter is set either
on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil". In addition, the
"Heating type" parameter must be set on "Free configuration".
Pos: 31.7.13 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleRegelung Heizen — I-Anteil (min.) @ 40\mod_1421679855627_15.docx @ 312528 @ 3 @ 1
11.3.10

Heating control - I-component (min.)

Options:
The I-component refers to the reset time of a control. The integral component has the effect of
moving the room temperature slowly toward, and ultimately reaching, the setpoint value.
Depending on the type of system used, the reset time has to have different values. In general,
the more inactive the overall system, the greater the reset time.
Note
This parameter is only available when "Control value type" parameter is set either
on "PI continuous, 0 – 100%", "PI PWM, On/Off" or "Fan coil". In addition, the
"Heating type" parameter must be set on "Free configuration".
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
PI continuous, 0 – 100% and PI PWM, On/Off:
Area (e.g. floor heating) 4°C 200 min
Convector (e.g. heater) 1.5°C 100 min
Free configuration
Fan coil:
Fan coil 4°C 90 min
Free configuration
Setting option between 10 - 100
Setting option between 0 - 255
objects
— 34 —

Advertisement

Table of Contents
loading

Table of Contents