11.3.39

Cooling control - Extended settings

Options:
This parameter enables additional functions and communication objects, e.g. "Basic stage
cooling".
Pos: 31.7.49 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Kühlen @ 40\mod_1421682149404_15.docx @ 312978 @ 3 @ 1
11.3.40

Basic stage cooling

Note
Only available when the "Extended settings" parameter under "Cooling control" is
set on "Yes".
Pos: 31.7.50 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Kühlen — Statusobjekt Kühlen @ 40\mod_1421682228449_15.docx @ 312993 @ 3 @ 1
11.3.41

Basic stage cooling - Status object cooling

Options:
This parameter enables the "Status cooling" communication object.
Pos: 31.7.51 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Kühlen — Wirksinn der Stellgröße @ 40\mod_1421682294859_15.docx @ 313008 @ 3 @ 1
11.3.42

Basic stage cooling - Mode of the control value

Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
Normal: Value 0 means "Valve closed".
Inverse: Value 0 means "Valve open".
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
No
Yes
No
Yes
Normal
Inverse
objects
— 45 —